Watt values are approximate, editable starting figures. Refer to the device nameplate; power ratings may vary between similar devices.
Select the devices you plan to use, calculate your total power requirement, and discover the right generator capacity.
Watt values are approximate, editable starting figures. Refer to the device nameplate; power ratings may vary between similar devices.
The electrical input power of all devices operating simultaneously is multiplied by their respective quantities and summed. A design margin is then added to this total running load to account for potential additional loads and future expansion—set to 20% by default. Finally, the total power is divided by the selected power factor to determine the required generator capacity (kVA). This figure serves as a preliminary sizing estimate; motor starting currents, alternator transient load response, and site conditions must also be evaluated during technical selection.
kW represents active (real) power, whereas kVA represents apparent power. Their relationship is defined as kW = kVA × power factor. At a power factor of 0.80, 100 kVA corresponds to 80 kW of active power. Both kW and kVA limits must be considered when selecting a generator; relying on a single value alone may not be sufficient.
Use the formula kVA = kW / power factor. For example, a 100 kW load with a 0.80 power factor requires 125 kVA of apparent power. This conversion alone does not include design margins or derating caused by ambient site conditions.
Use the formula kW = kVA × power factor. For example, at 125 kVA and a 0.80 power factor, active power equals 100 kW. The actual power factor of the equipment or system should be used in the calculation; 0.80 is not a fixed constant for all load types.
1 kVA corresponds to different kW values depending on the power factor. At a power factor of 0.80, 1 kVA = 0.80 kW; at a power factor of 1.0, 1 kVA = 1 kW. Therefore, a single conversion value cannot be stated without knowing the power factor.
A 100 kVA generator rated at a 0.80 nameplate power factor delivers 80 kW of active power in its designated duty class. However, Standby and Prime ratings may differ. Usable output must be evaluated alongside the manufacturer's datasheet, duty class, altitude, ambient temperature, and load characteristics.
Power factor is the ratio of active power to apparent power: PF = kW / kVA. Under sinusoidal voltage and current conditions, this ratio is expressed as cosφ; for nonlinear loads with harmonics, total power factor must be considered separately. For a given kW load, a lower power factor increases the required kVA. For instance, an 80 kW load requires 100 kVA at PF 0.80, compared to 80 kVA at PF 1.0.
Identify the input wattage, quantity, and simultaneous operating profile of all loads to be powered. Evaluate the design margin, power factor, and duty class together. You can update the approximate device wattages in this tool using actual nameplate ratings. In three-phase systems, phase balance, harmonics, altitude, and ambient temperature must also be checked for final sizing.
Standby refers to backup power applications during utility outages; Prime refers to operating as the primary power source under variable loads; Continuous refers to supplying constant, uninterrupted load under defined conditions. Permissible operating hours, average load factor, overload capability, and maintenance intervals vary according to the manufacturer's rating definitions. These ratings are not interchangeable and must follow the product datasheet.
By subscribing to our newsletter, you'll be the first to receive information about our new products, promotions, and industry developments. By subscribing, you acknowledge that you have read and accepted the Personal Data Protection Law (KVKK)
KJ Power is a well-established diesel generator manufacturer operating in the energy sector since 1996. The company, which produces a wide range of diesel generator sets from 10 kVA to 5000 kVA, has international ISO 9001:2015 and other important certificates. As a generator company, it provides special generators for projects by offering special engineering solutions. Serving many sectors in Turkey, KJ Power has proven its global success as a generator manufacturer by exporting 90% of its production to more than 120 countries.